Conventional Fire Alarm Panel LX-EFC802-28
LX-EFC802-28 is a 28-zone conventional fire alarm control panel from the LX-EFC802 series, supplied in a 61.5 x 38.4 x 10.5 cm cabinet. Each zone accepts up to 20 conventional heat or smoke detectors with no limit on manual call points, and two sounder circuits drive alarm devices through the panel. The 220-230VAC 50/60Hz supply is backed by automatic mains/standby switchover and a built-in charger for two 12V lead-acid batteries. Fault supervision covers mains, charger and batteries, and the front panel provides clear LED indications, functional buttons and an evacuation resound. The same platform covers 1 to 32 zones.
Key Product Specifications
• Analogue conventional detector inputs: 20 heat/smoke detectors
• No limit of manual call points per zone
• Automatic power switchover: mains power and stand-by power
• Standby battery backup with built-in charging
• External pushbuttons keyswitch activated
• Internal power supply 24VDC
• Auxiliary output 24VDC
• External LED indicators
• Fault supervision and notification: mains, charger and batteries
• Succinct functional buttons: friendly user interface for easy operation and recognition
• Automatic loading and testing of battery
• Line fault monitored for open circuit/short circuit
• End of line resistor supplied for sounder circuit
• Evacuation: alarm resound
• Color: Black or White
Technical Data
| Model | Number of Zones | Sounder Circuits | AC Input | DC Output | Battery | Operation Temperature | Humidity | Cabinet Size |
|---|---|---|---|---|---|---|---|---|
| LX-EFC802-1 | 1 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 1.2AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 27.3*20*7.7CM |
| LX-EFC802-2 | 2 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 1.2AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 31*25*10CM |
| LX-EFC802-3 | 3 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 1.2AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 31*25*10CM |
| LX-EFC802-4 | 4 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 1.2AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 31*25*10CM |
| LX-EFC802-5 | 5 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 410*318*105CM |
| LX-EFC802-6 | 6 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 410*318*105CM |
| LX-EFC802-7 | 7 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 410*318*105CM |
| LX-EFC802-8 | 8 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 410*318*105CM |
| LX-EFC802-9 | 9 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 410*318*105CM |
| LX-EFC802-10 | 10 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 410*318*105CM |
| LX-EFC802-11 | 11 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 410*318*105CM |
| LX-EFC802-12 | 12 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 410*318*105CM |
| LX-EFC802-13 | 13 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 513*318*105CM |
| LX-EFC802-14 | 14 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 513*318*105CM |
| LX-EFC802-15 | 15 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 513*318*105CM |
| LX-EFC802-16 | 16 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 513*318*105CM |
| LX-EFC802-17 | 17 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 513*318*105CM |
| LX-EFC802-18 | 18 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 513*318*105CM |
| LX-EFC802-19 | 19 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-20 | 20 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-21 | 21 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-22 | 22 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-23 | 23 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-24 | 24 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-25 | 25 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-26 | 26 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-27 | 27 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-28 | 28 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-29 | 29 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-30 | 30 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-31 | 31 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
| LX-EFC802-32 | 32 | 2 Circuits | 220V-230VAC 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | -10℃ to +40℃ | 5 to 95% RH, non-condensing | 615*384*105CM |
Why Choose Lixin LX-EFC802-28 Conventional Fire Alarm Panel?
28 Zones in One Panel
Twenty-eight independently supervised zones cover large buildings while keeping the proven LX-EFC802 interface.
20 Detectors per Zone
Up to 20 conventional detectors can be connected per zone, with no limit on manual call points.
Large 61.5 x 38.4 cm Cabinet
The larger enclosure provides room for wiring, batteries and the power supply in big installations.
- Quality: 100% Inspection
- Packaging: Export Standard Carton
- Service: Timely Full Support
Application Scenarios
LX-EFC802-28 Conventional Fire Alarm Panel Is Widely Used In
- Office Buildings – Office towers, business hubs and large-scale commercial complexes of all sizes
- Retail Stores – Shopping centers, retail stores and all customer-facing commercial premises
- Hospitality Venues – Hotels, restaurants and diversified commercial service and catering environments
- Residential Buildings – Apartments, condominiums and various multi-family residential housing units
- Hospital——Inpatient towers, outpatient clinics and various auxiliary medical support units
- Factory——Manufacturing plants, assembly workshops and various multi-purpose factory production units