Conventional Fire Alarm Panel LX-801-1

LX-801-1 is a 1-zone conventional fire alarm control panel from the LX-801 series. It accepts up to 20 conventional heat or smoke detectors per zone with no limit on manual call points, and provides two sounder circuits rated 24V nominal with a 10K end-of-line resistor. The panel runs on 240VAC ±10% 50/60Hz with a 24VDC typical output, automatic mains/standby switchover and a built-in charger for two 12V lead-acid batteries. Glass fuses protect the main supply, sounder outputs and charging circuit, while zoned red alarm and yellow trouble LEDs give clear status at a glance. The ivory 30 x 20 x 9.6 cm cabinet is part of a 1-36 zone range.

Key Product Specifications

• Analogue conventional detector inputs: 20 heat/smoke detectors
• No limit of manual call points per zone
• Charging voltage protection: 1.6Ah glass fuse
• Sounder output: 24V nominal, EOL 10K resistor
• Auxiliary contacts: 30VDC, 1A max. NC/NO
• Main supply protection: glass fuse
• Sounder protection: 2*500mA glass fuse
• Battery reversal protection via charger glass fuse
• Zone EOL: 5.6K resistor
• Zoned visual red alarm and yellow trouble indicators
• Continuous signal during alarm
• Standby battery backup with built-in charging
• Automatic power switchover: mains power and stand-by power
• Automatic testing: low / no power, battery status and loading test
• Evacuation: alarm resound
• Color: Ivory

Technical Data

ModelNumber of ZonesSounder CircuitsAC InputDC OutputBatteryOperation TemperatureHumidityCabinet Size
LX-801-112 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 1.2AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing30*20*9.6CM
LX-801-222 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 1.2AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing30*20*9.6CM
LX-801-332 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 1.2AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing30*20*9.6CM
LX-801-442 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 1.2AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing30*20*9.6CM
LX-801-552 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*32*9.6CM
LX-801-662 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*32*9.6CM
LX-801-772 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*32*9.6CM
LX-801-882 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*32*9.6CM
LX-801-992 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*32*9.6CM
LX-801-10102 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*32*9.6CM
LX-801-11112 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*32*9.6CM
LX-801-12122 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*32*9.6CM
LX-801-13132 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*44*9.6CM
LX-801-14142 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*44*9.6CM
LX-801-15152 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*44*9.6CM
LX-801-16162 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*44*9.6CM
LX-801-17172 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*44*9.6CM
LX-801-18182 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*44*9.6CM
LX-801-19192 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*44*9.6CM
LX-801-20202 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*44*9.6CM
LX-801-21212 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*56*9.6CM
LX-801-22222 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*56*9.6CM
LX-801-23232 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*56*9.6CM
LX-801-24242 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*56*9.6CM
LX-801-25252 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*56*9.6CM
LX-801-26262 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*56*9.6CM
LX-801-27272 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*56*9.6CM
LX-801-28282 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*56*9.6CM
LX-801-29292 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*68*9.6CM
LX-801-30302 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*68*9.6CM
LX-801-31312 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*68*9.6CM
LX-801-32322 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*68*9.6CM
LX-801-33332 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*68*9.6CM
LX-801-34342 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*68*9.6CM
LX-801-35352 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*68*9.6CM
LX-801-36362 Circuits240VAC±10% 50/60Hz24VDC typicalLead-acid 2.5AH/12V*2pcs0℃ to +40℃≤95% RH, non-condensing31*68*9.6CM

Why Choose Lixin LX-801-1 Conventional Fire Alarm Panel?

1-36 Zone Range

The LX-801 series scales from 1 to 36 zones in the same product family, covering small shops through large buildings.

Glass-Fuse Protection

Main supply, sounder outputs and the charging circuit are protected by replaceable glass fuses for safe operation.

Zoned Alarm & Trouble LEDs

Red alarm and yellow trouble indicators per zone make fault finding quick and straightforward.