Conventional Fire Alarm Panel LX-801-1
LX-801-1 is a 1-zone conventional fire alarm control panel from the LX-801 series. It accepts up to 20 conventional heat or smoke detectors per zone with no limit on manual call points, and provides two sounder circuits rated 24V nominal with a 10K end-of-line resistor. The panel runs on 240VAC ±10% 50/60Hz with a 24VDC typical output, automatic mains/standby switchover and a built-in charger for two 12V lead-acid batteries. Glass fuses protect the main supply, sounder outputs and charging circuit, while zoned red alarm and yellow trouble LEDs give clear status at a glance. The ivory 30 x 20 x 9.6 cm cabinet is part of a 1-36 zone range.
Key Product Specifications
• Analogue conventional detector inputs: 20 heat/smoke detectors
• No limit of manual call points per zone
• Charging voltage protection: 1.6Ah glass fuse
• Sounder output: 24V nominal, EOL 10K resistor
• Auxiliary contacts: 30VDC, 1A max. NC/NO
• Main supply protection: glass fuse
• Sounder protection: 2*500mA glass fuse
• Battery reversal protection via charger glass fuse
• Zone EOL: 5.6K resistor
• Zoned visual red alarm and yellow trouble indicators
• Continuous signal during alarm
• Standby battery backup with built-in charging
• Automatic power switchover: mains power and stand-by power
• Automatic testing: low / no power, battery status and loading test
• Evacuation: alarm resound
• Color: Ivory
Technical Data
| Model | Number of Zones | Sounder Circuits | AC Input | DC Output | Battery | Operation Temperature | Humidity | Cabinet Size |
|---|---|---|---|---|---|---|---|---|
| LX-801-1 | 1 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 1.2AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 30*20*9.6CM |
| LX-801-2 | 2 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 1.2AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 30*20*9.6CM |
| LX-801-3 | 3 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 1.2AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 30*20*9.6CM |
| LX-801-4 | 4 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 1.2AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 30*20*9.6CM |
| LX-801-5 | 5 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*32*9.6CM |
| LX-801-6 | 6 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*32*9.6CM |
| LX-801-7 | 7 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*32*9.6CM |
| LX-801-8 | 8 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*32*9.6CM |
| LX-801-9 | 9 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*32*9.6CM |
| LX-801-10 | 10 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*32*9.6CM |
| LX-801-11 | 11 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*32*9.6CM |
| LX-801-12 | 12 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*32*9.6CM |
| LX-801-13 | 13 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*44*9.6CM |
| LX-801-14 | 14 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*44*9.6CM |
| LX-801-15 | 15 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*44*9.6CM |
| LX-801-16 | 16 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*44*9.6CM |
| LX-801-17 | 17 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*44*9.6CM |
| LX-801-18 | 18 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*44*9.6CM |
| LX-801-19 | 19 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*44*9.6CM |
| LX-801-20 | 20 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*44*9.6CM |
| LX-801-21 | 21 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*56*9.6CM |
| LX-801-22 | 22 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*56*9.6CM |
| LX-801-23 | 23 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*56*9.6CM |
| LX-801-24 | 24 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*56*9.6CM |
| LX-801-25 | 25 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*56*9.6CM |
| LX-801-26 | 26 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*56*9.6CM |
| LX-801-27 | 27 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*56*9.6CM |
| LX-801-28 | 28 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*56*9.6CM |
| LX-801-29 | 29 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*68*9.6CM |
| LX-801-30 | 30 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*68*9.6CM |
| LX-801-31 | 31 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*68*9.6CM |
| LX-801-32 | 32 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*68*9.6CM |
| LX-801-33 | 33 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*68*9.6CM |
| LX-801-34 | 34 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*68*9.6CM |
| LX-801-35 | 35 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*68*9.6CM |
| LX-801-36 | 36 | 2 Circuits | 240VAC±10% 50/60Hz | 24VDC typical | Lead-acid 2.5AH/12V*2pcs | 0℃ to +40℃ | ≤95% RH, non-condensing | 31*68*9.6CM |
Why Choose Lixin LX-801-1 Conventional Fire Alarm Panel?
1-36 Zone Range
The LX-801 series scales from 1 to 36 zones in the same product family, covering small shops through large buildings.
Glass-Fuse Protection
Main supply, sounder outputs and the charging circuit are protected by replaceable glass fuses for safe operation.
Zoned Alarm & Trouble LEDs
Red alarm and yellow trouble indicators per zone make fault finding quick and straightforward.
- Quality: 100% Inspection
- Packaging: Export Standard Carton
- Service: Timely Full Support
Application Scenarios
LX-801-1 Conventional Fire Alarm Panel Is Widely Used In
- Office Buildings – Office towers, business hubs and large-scale commercial complexes of all sizes
- Retail Stores – Shopping centers, retail stores and all customer-facing commercial premises
- Hospitality Venues – Hotels, restaurants and diversified commercial service and catering environments
- Residential Buildings – Apartments, condominiums and various multi-family residential housing units
- Hospital——Inpatient towers, outpatient clinics and various auxiliary medical support units
- Factory——Manufacturing plants, assembly workshops and various multi-purpose factory production units